|

Presented with permission from Chemical Processing, September
1997.
By F. Greg Shinskey
Vessels known as
surge tanks are frequently located between process units for the
express purpose of smoothing flow variations. However, there is a
tendency in modern plants to minimize this inventory and, in some
cases, these vessels have been eliminated. Even when present they
are not always properly controlled, passing disturbances through
rather than attenuating them, and even producing cyclic flow
variations.

Fig. 1. A vessel having a time constant (holdup) of 100 min
has its level and outflow initially at 50%.
Unfortunately, in the presence of integral action, this
destabilizes the loop, producing long-term cycling. The problem
is illustrated in Fig. 1.
Liquid level is ordinarily easy to control by using a
conventional proportional-plus-integral (PI) controller. Using a
tight proportional band (high gain) can keep level near setpoint,
but this can cause the manipulated outflow to vary even more than
the inflow to the vessel. Short-term variations in outflow can be
reduced by widening the proportional band (reducing the
proportional gain) of the controller.
Here, a vessel having a time constant (holdup) of 100 min has
its level and outflow initially at 50%. At time zero, inflow to
the vessel suddenly drops to 30%, causing level and outflow to
begin falling. Integral action in the controller attempts to
restore the level to its setpoint of 50%, but can only do so by
actually reducing outflow below inflow, in this case overshooting
the inflow change by nearly 100%.
This overshoot not only amplifies the upset but also promotes
a lightly damped oscillation of 400-min period that will persist
for several cycles. In this simulation, the level controller had
a proportional band of 200% (a gain of 0.5) and an integral time
of 20 min.
The figure also shows the level and flow responses to the same
upset using a proportional-lag (P*) controller having a
proportional band of 80% and a lag time constant of 20 min. Note
that the resulting variation in outflow is less than for the PI
controller, and that no oscillation results—level and flow both
approach their new steady states exponentially.
The fundamental difference in the final steady states for the
two controllers is that the PI controller will eventually return
level to the 50% setpoint, whereas the P* controller allows the
level to change proportionally to the average flow.
This variation in level is a stumbling block for both
engineers and operators. The latter are accustomed to controlling
at setpoint in the steady state. When this does not happen, the
operators assume that the controller is not functioning properly.
Engineers assume that the optimum level is at the middle of
the tank, allowing the maximum margin for variation in both
directions.
In fact, the margin does not have to be the same in both
directions for all flowrates. At maximum inflow, the vessel can
be nearly full because there is little chance of inflow
increasing. At zero inflow it can be nearly empty. This is
accomplished by using proportional action with a band of 80%.
Outflow will be zero at 10% level and maximum at 90% level.
However, a true proportional controller, one having an
adjustable "manual reset" bias, must be used. The bias
and setpoint may both be set at 50%, or the setpoint may be
positioned at the low-level limit (e.g., 10%) and the bias at
zero. The latter is preferred to avoid expectations associated
with a 50% setpoint.
The lag may be placed on the level input to the controller or
in its output. It is not an essential function, simply providing
extra filtering for the flow. Proportional action is the
essential feature of the averaging level controller.
|